HSE guidance says the installer should have fitted an interlock between extraction and gas, and manual bypasses are not permitted. Work on gas fittings in a restaurant must be carried out by a Gas Safe registered engineer, and Regulation 35 puts the duty to keep appliances, pipework and flues safe on the employer.
What the film covers
- The gas nobody looks at until it matters
- Commercial kitchen gas regulations UK: who is bound
- Regulation 35: the maintenance duty
- Regulation 34: do not use an appliance you suspect is dangerous
- Competence and who may do the work
- Who may work on the gas: the commercial kitchen gas engineer
- How often: the gas safety certificate for restaurants
- What "CP42" means
Questions the film answers
- Is a gas safety certificate for restaurants a legal requirement?
The law requires gas appliances, pipework and flues to be maintained in a safe condition (regulation 35), and gas work must be done by a Gas Safe registered engineer. It sets no fixed interval or named certificate. HSE says annual inspection is "a reasonable minimum frequency". Some councils word it as a must for an annual record, so keep one.
- How much is a gas safety certificate for a commercial kitchen?
On the providers' own pages read on 17 November 2026, five appliances cost £263 excluding VAT at one firm (£153 plus two at £55) and £509.99 at another, which states no VAT wording. Repairs are extra, and so are re-inspections of failed items and parking or congestion charges. Get two written quotes and check how each counts appliances.
- What does a commercial kitchen gas engineer need to hold?
A Gas Safe registration with a current ID card, and for catering work a relevant certificate of competence for the type of equipment. HSE says the employer must check: use the Gas Safe Register website or phone 0800 408 5500, and ask to see the card. The card shows the work the engineer is qualified to do and whether qualifications are up to date.
- Do commercial kitchen gas interlock regulations apply to my older kitchen?
HSE's sheet says the installer should have fitted an interlock, manual bypasses are not permitted, and BS 6173 "is not retrospective". Where there is none, assess whether a risk is likely and prevent or control it. Some councils word it as a must for their areas. Ask your engineer to put the position in writing.
- Where should the commercial kitchen gas shut off valve be?
No official page read for this guide sets a rule on valve type or position. HSE's emergency wording starts with turning off the supply, so every shift needs to know where it is, and it should be labelled with 0800 111 999 beside it. Ask your engineer to identify and label it on your installation.
- Who is responsible for the gas if I rent the unit?
Regulation 35 follows control of the place of work, so a tenant who runs the kitchen is normally the employer under the duty. The landlord's 12-month check and 28-day record apply to residential premises, such as a flat above the restaurant. Who pays for the kitchen inspection is a lease question, so read the repairing covenants and agree it in writing.